Standards
UNE 211034 & IEC 60502-1
(Construction and tests)
LOW VOLTAGE DIRECTIVE: 2014/35 / EU
CPR Regulation (EU) No 305/2011:
Reaction to fire (Cca-s1a,d1,a1)
RoHS compliant
Quality certificate




Technical characteristics & performances
-
Single-core
-
Multicore
-
Bunched conductor (class 5) mm2
-
Maximum service temperature: 70ºC / 160ºC
-
0,6/1 (1,2) kV C.A
-
Low temperature resistance
-
Easy peeling / easy strip
-
Protection against Electromagnetic disturbances
Fire performance
-
Flame retardant
-
Fire retardant
-
Low heat emission
-
Low production of flaming droplets
-
Low opacity & production of smoke
-
Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
-
Halogen free
-
Low emission of toxic gases
Uses and applications
-
Control & command
-
Distribution networks
-
Installations with risk of fire or explosion
-
BD2, BD3, BD4 (skyscrapers, tunnels…)
-
Buildings receiving the public
-
Industral use
-
Outdoor use
-
Instrumentation
Packaging
-
Drum
DOWNLOADS:
Technical DatasheetFunctional features
-
Technical designation:
Z1C4Z1-K (AS) 0,6/1 kV
-
Constructive description:
UNE 211034 & ref. IEC 60502-1 (Construction and tests)
- CONDUCTOR: Flexible, annealed, plain copper conductor, class 5 based on International standard IEC 60228.
- INSULATION: Thermoplastic halogen free compound, type TI 7 (EN 50363-7).
ASSEMBLY OF CONDUCTORS: In multicore cables, the cores are cabled helically.
- SHIELD: Al/PET tape + tinned copper braid. Coverage 100%.
- OVERSHEATH: Thermoplastic halogen free compound, ST8 (IEC 60502-1).
Colour: green
Identification of cores HD 308 S2:
2x - brown & blue
3x - brown, black & gray
3G - brown, blue & yellow / green
4x - brown, black, gray & blue
4G - brown, black, gray & yellow / green
5G - brown, black, gray, blue & yellow / green -
Rated voltage:
0.6/1 kV
-
Normal operation temperature:
70ºC
-
Short-circuit temperature (5 s max):
160ºC (t<5s)
-
Voltage test:
3,5 kV (5 min)
-
Colour:
Green (oversheath). Core identification acc. to HD 308 S2.
-
Fire performance:
- Reaction to fire: Cca-s1a,d1,a1 (EN 50575:2014+A1:2016)
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((EU) Nº 305/2011) articles 8 and 9. -
Type of installation:
Fixed
-
User´s guide:
Afirenas SHIELD Z1C4Z1-K 0,6/1 kV control & instrumentation cables are specially indicated for its use in distribution networks, power stations, tunnels, skyscrapers or public concurrence places and other electrical installations where a good fire performance and protection against electromagnetic interference (EMC) are necessary.
-
Technical instructions:
.
-
Conductor:
Flexible
-
Halogen free:
Yes
-
Armoured cable:
No