Afirenas CC-Z H07Z-R

Standards

EN 50525-3-41 (Construction & tests)
AENOR <HAR> certification

Low voltage Directive (L.V.D.):
2014/35/UE

CPR REGULATION 305/2011/UE:
Reaction to fire: Cca-s1a,d1,a1 (s=10mm2

IEC 60332-3-24; EN 60332-3-24
Fire retardant

RoHS compliant

Quality certificate

Certificate icon AENOR <HAR> certificationCertificate icon Low voltage Directive (LVD): 2014/35/EUCertificate icon CPR compliantCertificate icon RoHS

Technical characteristics & performances

  • Single-core Propiedad del cable: Single-core
  • Stranded conductor (class 2) mm2 Propiedad del cable: Stranded conductor (class 2) mm2
  • Maximum service temperature: 90ºC / 250ºC Propiedad del cable: Maximum service temperature: 90ºC / 250ºC
  • 450 / 750 V C.A. Propiedad del cable: 450 / 750 V C.A.
  • Easy peeling / easy strip Propiedad del cable: Easy peeling / easy strip

Fire performance

  • Flame retardant Propiedad del cable: Flame retardant
  • Fire retardant Propiedad del cable: Fire retardant
  • Low heat emission Propiedad del cable: Low heat emission
  • Low production of flaming droplets Propiedad del cable: Low production of flaming droplets
  • Low opacity & production of smoke Propiedad del cable: Low opacity & production of smoke
  • Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm Propiedad del cable: Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
  • Halogen free Propiedad del cable: Halogen free
  • Low emission of toxic gases Propiedad del cable: Low emission of toxic gases

Uses and applications

  • Panel and appliance wiring Propiedad del cable: Panel and appliance wiring
  • Residential use Propiedad del cable: Residential use
  • Indoor use Propiedad del cable: Indoor use

Packaging

  • Coil Propiedad del cable: Coil


Functional features

  • Technical designation:
    H07Z-R
  • Constructive description:
    EN 50525-3-41 (Construction and tests)

    CONSTRUCTION DESCRIPTION:
    Single core non-sheathed cables with halogen-free crosslinked insulation and low emission of smoke
    - CONDUCTOR:
    Rigid annealed plain copper conductor, class 1 (cross sectional areas: 1,5/2,5/4 mm2 – solid (-U)) or class 2 (cross sectional area ≥ 6 mm2 – stranded (-R)) acc. to IEC 60228; EN 60228.
    - INSULATION:
    Halogen free cross-linked polyolefin compound (Type EI 5) acc. to EN 50363-5.

    Number of cores: 1
    Cross-sectional area size range: 1,5 to 150 mm2.
  • Rated voltage:
    450/750 V
  • Normal operation temperature:
    90ºC
  • Short-circuit temperature (5 s max):
    250ºC
  • Voltage test:
    2,5 kV
  • Colour:
    *INSULATION: black, brown, gray, blue, yellow-green, red, white. Other colours on request.
  • Fire performance:
    Reaction to fire:  Cca-s1b, d1, a1 (EN 50575:2014+A1:2016)
       • EN 60332-1-2; IEC 60332-1 (H≤425 mm)  Flame retardant
       • EN 50399 (flame source: 20,5 kW) Fs ≤ 2 m  Fire retardant
       • Low heat generation: EN 50399 (flame source: 20,5 kW)
             - Total heat released: THR ≤ 30 MJ 
             - Maximum value of the heat released: Peak HRR ≤ 60 kW
             - Indication of heat increase: FIGRA ≤ 300 W/s
       • Low production and opacity of emitted smokes:
             - s1 (EN 50399):
                -Total smoke production: (TSP) ≤ 50 m2
                -Maximum value of smokes released : (Peak SPR) ≤ 0,25 m2/s
             - s1a: s1 and transmittance > 80 % (UNE EN 61034-2; IEC 61034-2)
       • Low production of flaming droplets (EN 50399 - flame source:20,5 kW):
             - d1: No flaming droplets/particles persisting longer than 10' occurs within 1200'.
       • Low acidity and conductivity of the emitted gases:
             - a1: pH≥4,3 conductivity < 2,5 microS/mm (EN 60754-2; IEC 60754-2)

    For covered range (+ information), please check out "CPR/DoP" section in our website.
    *The packaging labels of these cables include the CE marking according to the CPR Regulation ((UE) Nº 305/2011) articles 8 and 9.


    Other performances:
    Fire retardant: UNE EN 60332-3-24 / IEC 60332-3-24 (cat.C)
    Halogen free. Low emission of toxic gases: UNE EN 60754-1 / IEC 60754-1
  • Type of installation:
    Fixed
  • User´s guide:
    In locations where a low level of emission of smoke and corrosive gases are required in case of fire or burning. Installation in surface-mounted or embedded conduits, or similar closed systems.
    They are recommended for fixed and protected installation in lighting and control gear for voltages up to and including 1.000 V A.C or up to 750 V D.C. to earth.
    (EN 50565-2)

    They are suitable for internal wiring in electrical panel boards or electric meter.
  • Technical instructions:
    .
  • Conductor:
    Rigid
  • Halogen free:
    Yes
  • Armoured cable:
    No