Standards
EN 50525-3-41 (Construction & tests)
AENOR <HAR> certification
Low voltage Directive (L.V.D.): 2014/35/UE
CPR REGULATION 305/2011/UE:
Reaction to fire: Cca-s1a,d1,a1 (s=10mm2)
IEC 60332-3-24; EN 60332-3-24
Fire retardant
RoHS compliant
Quality certificate




Technical characteristics & performances
-
Single-core
-
Stranded conductor (class 2) mm2
-
Maximum service temperature: 90ºC / 250ºC
-
450 / 750 V C.A.
-
Easy peeling / easy strip
Fire performance
-
Flame retardant
-
Fire retardant
-
Low heat emission
-
Low production of flaming droplets
-
Low opacity & production of smoke
-
Low acidity & conductivity of the gases: pH<4,3 2,5 µS/mm
-
Halogen free
-
Low emission of toxic gases
Uses and applications
-
Panel and appliance wiring
-
Residential use
-
Indoor use
Packaging
-
Coil
Functional features
-
Technical designation:
H07Z-R
-
Constructive description:
EN 50525-3-41 (Construction and tests)
CONSTRUCTION DESCRIPTION:
Single core non-sheathed cables with halogen-free crosslinked insulation and low emission of smoke
- CONDUCTOR:
Rigid annealed plain copper conductor, class 1 (cross sectional areas: 1,5/2,5/4 mm2 – solid (-U)) or class 2 (cross sectional area ≥ 6 mm2 – stranded (-R)) acc. to IEC 60228; EN 60228.
- INSULATION:
Halogen free cross-linked polyolefin compound (Type EI 5) acc. to EN 50363-5.
Number of cores: 1
Cross-sectional area size range: 1,5 to 150 mm2. -
Rated voltage:
450/750 V
-
Normal operation temperature:
90ºC
-
Short-circuit temperature (5 s max):
250ºC
-
Voltage test:
2,5 kV
-
Colour:
*INSULATION: black, brown, gray, blue, yellow-green, red, white. Other colours on request.
-
Fire performance:
- Reaction to fire: Cca-s1b, d1, a1 (EN 50575:2014+A1:2016)
• EN 60332-1-2; IEC 60332-1 (H≤425 mm) Flame retardant
• EN 50399 (flame source: 20,5 kW) Fs ≤ 2 m Fire retardant
• Low heat generation: EN 50399 (flame source: 20,5 kW)
- Total heat released: THR ≤ 30 MJ
- Maximum value of the heat released: Peak HRR ≤ 60 kW
- Indication of heat increase: FIGRA ≤ 300 W/s
• Low production and opacity of emitted smokes:
- s1 (EN 50399):
-Total smoke production: (TSP) ≤ 50 m2
-Maximum value of smokes released : (Peak SPR) ≤ 0,25 m2/s
- s1a: s1 and transmittance > 80 % (UNE EN 61034-2; IEC 61034-2)
• Low production of flaming droplets (EN 50399 - flame source:20,5 kW):
- d1: No flaming droplets/particles persisting longer than 10' occurs within 1200'.
• Low acidity and conductivity of the emitted gases:
- a1: pH≥4,3 conductivity < 2,5 microS/mm (EN 60754-2; IEC 60754-2)
For covered range (+ information), please check out "CPR/DoP" section in our website.
*The packaging labels of these cables include the CE marking according to the CPR Regulation ((UE) Nº 305/2011) articles 8 and 9.
Other performances:
- Fire retardant: UNE EN 60332-3-24 / IEC 60332-3-24 (cat.C)
- Halogen free. Low emission of toxic gases: UNE EN 60754-1 / IEC 60754-1 -
Type of installation:
Fixed
-
User´s guide:
In locations where a low level of emission of smoke and corrosive gases are required in case of fire or burning. Installation in surface-mounted or embedded conduits, or similar closed systems.
They are recommended for fixed and protected installation in lighting and control gear for voltages up to and including 1.000 V A.C or up to 750 V D.C. to earth.
(EN 50565-2)
They are suitable for internal wiring in electrical panel boards or electric meter. -
Technical instructions:
.
-
Conductor:
Rigid
-
Halogen free:
Yes
-
Armoured cable:
No